Cleanroom Air Changes per Hour (ACH): How to Calculate and Select the Right Airflow
Cleanroom Airflow Calculation, AHU Selection & Contamination Control
ACH is an important cleanroom HVAC design parameter, but it should be evaluated together with cleanliness class, contamination load, airflow pattern, filtration and pressure control.
Air Changes per Hour describes how many times the equivalent room air volume is supplied to the cleanroom during one hour.
Higher airflow can improve contaminant dilution and recovery performance, but excessive airflow increases fan power, HEPA filter pressure drop, cooling load and overall HVAC system cost.
The design objective is therefore to provide sufficient airflow to meet cleanliness and process requirements without unnecessarily increasing energy consumption.
What Is Cleanroom ACH?
ACH represents the relationship between total cleanroom supply airflow and room volume.
ACH = Total Supply Airflow ÷ Room Volume
For example, if a cleanroom has a volume of 300 m³ and the HVAC system supplies 6,000 m³/h:
6,000 m³/h ÷ 300 m³ = 20 ACH
The cleanroom therefore receives an equivalent supply-air volume of approximately 20 room volumes per hour.
Why ACH Matters in Cleanroom HVAC Design
Cleanrooms continuously receive contamination from people, processes, equipment and materials.
Filtered supply air helps dilute and remove airborne contaminants through the room airflow and return-air system.
- Airborne particle dilution
- Contamination removal
- Room recovery performance
- Temperature distribution
However, higher airflow also increases the energy and equipment requirements of the HVAC system.
- Fan power consumption
- HEPA filter pressure drop
- Cooling and heating loads
- Air-handling equipment size
- Duct dimensions
- Operating cost
Does Every Cleanroom Class Have a Fixed ACH?
No.
ISO 14644-1 primarily classifies cleanrooms according to airborne particle concentration. It does not provide one mandatory ACH value for every ISO cleanliness class.
Actual airflow should be determined according to the complete contamination-control requirement.
- Required cleanliness classification
- Process contamination generation
- Number of operators
- Equipment particle and heat loads
- Air distribution pattern
- HEPA / ULPA filtration arrangement
- Required recovery time
- Room dimensions and ceiling height
How to Calculate Cleanroom Supply Airflow
If the target ACH has been established through the cleanroom design process, required airflow can be calculated from the room volume.
Supply Airflow = Floor Area × Ceiling Height × ACH
Calculation Example
| Design Parameter | Value |
| Floor Area | 200 m² |
| Ceiling Height | 3 m |
| Room Volume | 600 m³ |
| Design ACH | 20 |
| Required Supply Airflow | 12,000 m³/h |
From ACH Calculation to AHU Selection
Once the required supply airflow has been determined, it becomes one of the major inputs for HVAC equipment selection.
Cleanroom Requirements
↓
Room Volume
↓
Design ACH / Airflow Requirement
↓
Total Supply Airflow
↓
HEPA Filter Layout
↓
Duct & Pressure Calculation
↓
AHU Selection
ACH and Cleanroom Ceiling Height
Ceiling height directly affects calculated ACH because room volume increases as height increases.
Two cleanrooms with the same floor area and the same supply airflow can therefore have different ACH values if their ceiling heights are different.
This becomes especially important in high-bay cleanrooms.
High spaces should not automatically use the same ACH rules of thumb applied to conventional cleanrooms. Airflow velocity, contamination source height and supply/return air distribution may provide a more useful basis for system design.
ACH Is Only One Part of Cleanroom Design
Cleanliness Classification
The required airborne particle concentration determines the overall contamination-control strategy.
Fresh Air & Exhaust Balance
Outdoor air is required to compensate for exhaust air, provide ventilation and support room pressure relationships.
Room Pressure Control
Controlled pressure differentials help limit unwanted contamination migration between spaces with different cleanliness requirements.
Airflow Pattern
Non-unidirectional, unidirectional and mixed airflow systems use different contamination-control strategies and should not be designed using ACH alone.
HEPA / ULPA Filtration
Filter efficiency, filter area, face velocity and pressure drop directly affect cleanroom performance and fan selection.
Recovery Time
Some cleanrooms require rapid restoration of the specified cleanliness condition after personnel activity or other contamination events.
HEPA Filter Quantity and Airflow
After the total airflow is established, the designer must determine how that airflow will be distributed through the terminal filtration system.
HEPA filter selection should consider:
- Total room airflow
- Individual filter rated airflow
- Filter face velocity
- Pressure drop
- Ceiling coverage
- Required airflow pattern
- Cleanroom layout and contamination sources
Static Pressure Is Critical for Cleanroom AHU Selection
High airflow alone is not enough to select an AHU.
The fan must also overcome the resistance of the complete cleanroom air-distribution system.
- Supply duct resistance
- Return duct resistance
- HEPA filter pressure drop
- Terminal housings
- Dampers and valves
- Elbows and fittings
- Return-air grilles
- Other project-specific components
The selected fan should therefore be verified at the required airflow and required external static pressure, rather than using maximum airflow alone.
Cleanroom Pressure Relationships
Cleanroom airflow design also determines how much air enters and leaves each space.
The balance between supply, return and exhaust airflow influences room pressure.
Supply Air
↓
Cleanroom
↓
Return Air + Exhaust Air + Transfer Air
↓
Required Room Pressure Relationship
Why Excessive ACH Is Not Always Better
Using substantially more airflow than required can increase operating cost without providing a proportional improvement in cleanliness.
Excessive airflow may also increase:
- Fan power
- Filter replacement frequency
- HVAC noise
- Cooling-coil capacity
- Duct dimensions
- Initial project investment
Cleanroom optimization therefore requires balancing contamination control with energy and system performance.
YUJU Cleanroom Air Handling Solutions
YUJU EnvironTech supports laboratories, controlled production areas and specialized clean environments with customized air-handling and HVAC system solutions.
Our approach evaluates the complete air system rather than selecting an AHU from nominal airflow alone.
- Cleanroom airflow calculation
- ACH review
- AHU selection
- Heating and cooling load review
- HEPA filtration configuration
- Supply and return air planning
- Static-pressure calculation
- Temperature and humidity control
- Room pressure strategy
- HVAC automation and monitoring
What Information Should You Provide?
- Cleanroom application
- Required cleanliness classification
- Room dimensions and ceiling height
- Number of operators
- Process equipment and heat load
- Exhaust airflow
- Temperature requirement
- Humidity requirement
- Required pressure relationship
- Recovery-time requirement where applicable
- Project location
Frequently Asked Questions
Does higher ACH always mean a cleaner cleanroom?
Not necessarily. Higher airflow can improve particle dilution, but actual cleanroom performance also depends on filtration, contamination generation, airflow distribution, room pressure and operating procedures.
How is cleanroom ACH measured?
Total supply airflow can be measured at the terminal filters or supply outlets and divided by the cleanroom volume to calculate ACH.
Does ISO 14644-1 specify a fixed ACH for every cleanroom class?
No. ISO 14644-1 classifies cleanrooms primarily according to airborne particle concentration rather than assigning one fixed ACH value to every cleanliness class.
How should high-bay cleanrooms be designed?
High-bay spaces should consider airflow velocity, process height, contamination-source location and supply/return airflow distribution rather than relying only on conventional ACH rules of thumb.
Can YUJU help select a cleanroom AHU?
YUJU can support airflow, static-pressure, filtration and temperature/humidity requirements to coordinate suitable cleanroom air-handling equipment for the project.
YUJU EnvironTech
Cleanroom AHU & Airflow Engineering Solutions
ACH | AHU | HEPA | Pressure Control | Temperature & Humidity | HVAC Automation



Scan Contact Us